Use PLC4x to connect to a Siemens S7 PLC
Shifu is also compatible with Siemens S7 series
PLCs in the form of PLC4X. This article will show you how to use deviceshifu-plc4x-http
to integrate and interact with a Siemens S7-1200 1214C PLC
.
Connection
Step 1
Before connecting to Shifu, the PLC should already be physically connected to the host computer running Shifu via Ethernet and have an IP address, here we use 192.168.0.1
.
If the IP address of your PLC device is not 192.168.0.1
, you can change address
in the edgedevice-plc4x.yaml
file to the IP of your device)
Step 2
Create a folder, which in the example we named plc4x_configuration_directory
. Save all four configuration files described below in this folder.
First we need a configuration file to get the IP address and device type.
click here to check deviceshifu-plc4x-deployment.yaml
apiVersion: apps/v1
kind: Deployment
metadata:
labels:
app: deviceshifu-plc4x-deployment
name: deviceshifu-plc4x-deployment
namespace: deviceshifu
spec:
replicas: 1
selector:
matchLabels:
app: deviceshifu-plc4x-deployment
template:
metadata:
labels:
app: deviceshifu-plc4x-deployment
spec:
containers:
- image: edgehub/deviceshifu-http-plc4x:v0.1.1
name: deviceshifu-http
ports:
- containerPort: 8080
volumeMounts:
- name: deviceshifu-config
mountPath: "/etc/edgedevice/config"
readOnly: true
env:
- name: EDGEDEVICE_NAME
value: "edgedevice-plc4x"
- name: EDGEDEVICE_NAMESPACE
value: "devices"
volumes:
- name: deviceshifu-config
configMap:
name: plc4x-configmap
serviceAccountName: edgedevice-sa
In the mean time, we need some common configuration files:
click here to check deviceshifu-plcs4x-configmap.yaml
apiVersion: v1
kind: ConfigMap
metadata:
name: plc4x-configmap
namespace: deviceshifu
data:
driverProperties: |
driverSku: testPlc4x
driverImage:
instructions: |
instructions:
telemetries: |
telemetrySettings:
click here to check deviceshifu-plc4x-service.yaml
apiVersion: v1
kind: Service
metadata:
labels:
app: deviceshifu-plc4x-deployment
name: deviceshifu-plc4x
namespace: deviceshifu
spec:
ports:
- port: 80
protocol: TCP
targetPort: 8080
selector:
app: deviceshifu-plc4x-deployment
type: LoadBalancer
click here to check edgedevice-plc4x.yaml
apiVersion: shifu.edgenesis.io/v1alpha1
kind: EdgeDevice
metadata:
name: edgedevice-plc4x
namespace: devices
spec:
sku: "testPlc4x"
connection: Ethernet
address: 192.168.0.1 #change this accordingly
protocol: PLC4X
protocolSettings:
PLC4XSetting:
protocol: s7
Step 3
Add PLC devices in Shifu,build and start deviceShifu:
kubectl apply -f ../plc4x_configuration_directory
Operations
Shifu can read and write to the memory of PLC via HTTP requests.
Before operation, we need to start an nginx container
for sending and receiving HTTP requests, the relevant command to start is as follows:
kubectl run nginx --image=nginx:1.21 -n deviceshifu
kubectl exec -it nginx -n deviceshifu -- bash
deviceshifu-plc4x-http
has two built-in commands read
and write
, which we can use to read and write to the devices via shifu.
The command %Q0.0:BOOL
in this article is a PLC4X command where Q
is the name of the memory area, 0.0
indicates the address of the starting bit and its offset. BOOL
is the type of data to be read (written).
If you want to know more about PLC4X commands, please go to PLC4X official website.
read
read means to read the value of the device using the corresponding command:
For example, the command curl "deviceshifu-plc4x/read?%Q0.0:BOOL"
returns the address of the memory area Q0
.
curl "deviceshifu-plc4x/read?%Q0.0:BOOL"; echo
{"field_%Q0.0:BOOL": "BOOL(1bit):false"}
At this point Shifu returns the status of the first indicator from left to right in the Q area. If the light is on, then it returns true, otherwise it returns false. Since the light is off, the return value is false.
write
write
means to modify the value of the corresponding location through commands:
For example, the command curl "deviceshifu-plc4x/write?%Q0.0:BOOL=true"
will change the first bit of Q0
to true.
curl "deviceshifu-plc4x/write?%Q0.0:BOOL=true"; echo
More
If you need to read or write multiple commands at the same time, you can connect them with &
.
For example, the command curl "deviceshifu-plc4x/read?%Q0.0:BOOL&%Q0.1:BOOL"
will return both the first bit and the second bit of Q0
at the same time.
The command curl "deviceshifu-plc4x/write?%Q0.0:BOOL=true&%Q0.1:BOOL=true"
will change both the first bit and the second bit of Q0
to true.